The Honeywell System Sensor COSMOD2W i4 series module is designed to interface between compatible i4 series combination CO/smoke detectors (Model COSMO-2W and COSMO-4W) and compatible security/fire panels. It can also be used to retrofit compatible i4 series detectors into an existing loop of i3 smoke detector models 2WTA-B or 4WTA-B, without adding wires. The module interprets signals and translates them into a separate smoke zone and a separate CO zone, each with alarm and trouble signals. The module will interconnect the detectors connected to it and alarm them in either Temporal 3 or Temporal 4 pattern. Optional triggers are provided to initiate multiple modules to sound. (an additional RSSMOD is not required) Local status indication is provided by 4 LED's and a 3 position DIP switch enables user configuration.
The i4 COSMOD2W, 2-wire interface module, offers additional functionality including:
Ability to query for a "need for maintenance" condition from 2-wire i4 series model COSMO-2W and i3 series model 2WTA-B smoke detectors
One relay is available to indicate a multitude of maintenance conditionsat the control panel
All conditions are displayed at the module and at the detector
EZ Walk test mode allows the installer to easily verify that all detectors on a loop are operational
Allows 2-wire smoke detectors to be used on any compatible 4-wire control panel and provides Style D / Class A wiring on the detector loop
Allows up to 12 compatible devices including the i4 series combination CO/smoke detector to be integrated with a panel
Activates sounders of all detectors on loop in either Temporal 3 or Temporal 4 pattern